Electric High Temperature Control Valve

Electric high-temperature control valve shown in the supplier catalog

The supplier catalog lists this item as Electric High Temperature Control Valve in the Control Valve series on PDF pages 100–101. It confirms the valve type and electric actuation, but does not publish a verified operating-temperature limit, flow capacity, pressure rating, material grade, connection or actuator package. Use the operating cases and control-system details below to request a configuration-specific review.

Product identity

Catalog identity and source

This page identifies one supplier-catalog item within the VALMORA Control Valves range. Use the parent category to compare control-valve routes; use this record to reference the exact catalog identity. It is not a complete technical datasheet or approval of a project duty.

Product family

Control Valve — the parent route for browsing the wider control-valve range.

Catalog series

Control Valve — the source-series label printed in the recovered supplier catalog.

Evidence source

Recovered English supplier catalog, PDF pages 100–101. The verified product image is AST-R1-0334 on PDF page 101.

Catalog evidence

Catalog-documented product data

Only fields stated by the supplier catalog are shown as product data. The words “high temperature” identify the catalog item; they do not establish an operating-temperature limit. The label also does not publish a size, pressure rating, material grade, connection, applicable standard, flow capacity or actuator specification.

FieldCatalog-documented valueEvidence status
Valve typeControl ValveVERIFIED — PDF catalog label
ActuationElectricVERIFIED — PDF catalog label
Catalog source seriesControl ValveVERIFIED — PDF catalog section
Catalog source pagePDF pages 100–101VERIFIED — recovered PDF mapping

Important: unlisted values remain unconfirmed until the offered model-specific datasheet and approved order drawing identify the exact configuration.

Evidence boundary

Catalog facts and open configuration fields

The catalog confirms the product identity, source series and electric actuation. It does not define the internal construction, service envelope, shutoff performance or complete actuator package of the item shown.

Confirmed by the catalog

Confirm before quotation

Engineering review

How to specify the Electric High Temperature Control Valve

Selection requires a matched process duty and a defined control assembly. A valve that fits the line may still be incorrectly sized for the required flow range, and an electric actuator may not support the available control signal or required failure response. Supply the inputs below before comparing quotations.

Flow cases and pressure drop

Provide minimum, normal and maximum flow with the matching upstream and downstream pressures for each case; the pressure drop must be assessed for each paired operating point. State units and whether pressures are gauge or absolute. For gas or vapor volumetric flow, identify actual or standard volume and give the reference temperature and pressure for standard values. Include startup, turndown and upset cases if they change the required control range. Do not pair maximum flow with unrelated pressure data. Ask the supplier to show the sizing basis, selected trim and expected travel across the cases; line size alone cannot establish controllability.

Temperature and pressure envelope

State process operating and design temperatures and pressures, including startup/shutdown, thermal cycling, transients and any vacuum case. Request the quoted body’s pressure–temperature limits and the proposed trim, packing and bonnet/stem arrangement for those conditions. Check the electric actuator and positioner ambient limits separately from process temperature; the catalog title does not establish any of these limits.

Materials and piping interface

Confirm body, trim, seat, packing and other wetted materials against the actual fluid and temperature. Provide line size, end connection, applicable dimensional standard, mating interface, flow direction and dimensional constraints. No material grade, connection or construction detail is established by the catalog label.

Electric actuator and control signal

Specify the available power supply and control-system output, including whether commands are discrete or analog and the actual signal range/interface. State whether the duty is modulating or on/off, plus required movement time, duty cycle, position feedback, local/remote control and enclosure/site conditions. Ask the supplier to confirm that the actuator and any positioner/controller are compatible with the control system and selected valve.

Shutoff and loss-of-power behavior

Modulating control and isolation are separate duties. If the valve must shut off, state the permitted seat leakage and the applicable acceptance/test basis. Separately define the required position on loss of power, loss of control signal and any ESD/interlock command. An electric actuator is not automatically fail-open or fail-closed; confirm fail-in-place or a documented stored-energy/spring-return arrangement and the resulting valve position.

Inspection and documents

Request the model-specific datasheet, outline/end-connection drawing and supplier sizing basis for the quoted duty. List required material records, pressure and seat-leakage tests, inspection points, marking and any third-party witness requirements. Confirm the applicable standard and edition, inspection scope and records included in the offer; catalog wording is not a test certificate.

Application and installation

Match the control loop and installation to the service

The product name is only a catalog starting point. The process variable, fluid properties, control-loop arrangement and installation environment determine what must be checked in the proposed assembly.

Service medium

Identify the fluid phase, composition and concentration, plus density or viscosity data where available, solids, corrosive or erosive constituents and cleaning requirements. These properties affect capacity calculations, trim selection and material compatibility.

Control loop and system function

Describe the plant function and controlled variable—flow, pressure or temperature. Identify the measurement point, manipulated stream, expected load changes and relevant upstream/downstream equipment. An industry name alone does not define the control duty or prove this catalog item is suitable.

Pneumatic Piston High Temperature Control Valve

A separate pneumatic high-temperature route listed in the parent catalog. Compare the available instrument-air supply, control interface, required fail action and model-specific datasheet; do not transfer this electric model’s evidence to it.

Installation and thermal environment

Confirm orientation, flow direction, piping loads and support, available space, maintenance access and ambient conditions at the electric actuator/positioner. For hot service, ask the supplier to show how the selected bonnet, stem and packing arrangement manages process heat; do not infer an extension design from the catalog image.

Buyer questions

Electric High Temperature Control Valve FAQ

These answers separate catalog-confirmed identity from the operating and control requirements that need a model-specific response.

What does the supplier catalog confirm?

It identifies the product as Electric High Temperature Control Valve in the Control Valve series and confirms electric actuation. The mapped product image is AST-R1-0334 on PDF page 101. The catalog does not establish a numerical temperature limit, material grade, pressure rating, connection or complete actuator package.

How should the valve be sized for the process duty?

Provide minimum, normal and maximum flow with the corresponding upstream and downstream pressures for each case, plus fluid properties and the control objective. State whether pressures are gauge or absolute; for gas or vapor volumetric flow, identify actual or standard basis and the reference temperature and pressure. Ask the supplier to return the sizing basis, selected trim and expected travel across the operating cases. Do not size the valve from pipe diameter alone.

Does an electric actuator automatically move to a safe position when power is lost?

No. The result depends on the actuator design and any stored-energy or spring-return arrangement. Specify the required position for power loss, control-signal loss and any ESD/interlock command separately, then ask the supplier to identify how each response is achieved and documented.

What should be included in the RFQ?

Include the control objective, fluid and operating cases, paired flow and pressure data, temperature and pressure envelope, line and connection details, material requirements, electric supply and control interface, shutoff leakage and failure-position requirements, quantity, drawings, tests and inspection records.