El catálogo del proveedor identifica este artículo como Pneumatic Stainless Steel High Temperature Flanged Butterfly Valve on PDF page 95. The catalog confirms the product label and appearance only; it does not publish a numerical process-temperature limit, pressure-temperature curve, seat material or actuator ambient rating. Use the catalog identity to start the review, then verify the offered valve and actuator package against the actual duty.

Identidad del producto

Qué identifica el registro del catálogo

Esta página representa una identidad de catálogo documentada. No sustituye a la categoría de producto principal y no declara un modelo, una clasificación ni un historial de proyecto no verificados.

Familia de producto

Válvula de mariposa. Esta es la ruta comercial principal para la selección a nivel de categoría.

Serie de catálogo

Válvula de mariposa. Este es el contexto de la serie de origen impreso en el catálogo de productos recuperado.

Fuente de evidencia

Recovered supplier English product catalog, PDF page 95; mapped product image AST-R1-0305.

Evidencia del catálogo

Datos de producto documentados en catálogo

Solo los campos indicados en la etiqueta del catálogo PDF se muestran como datos del producto. Un término descriptivo como alta presión, gran diámetro o ASME no genera una clasificación numérica, un rango pedible ni una declaración de certificación.

CampoValor documentado en catálogoEstado de la evidencia
Tipo de válvulaVálvula de mariposaVERIFICADO — etiqueta del catálogo PDF
Descriptor de materialAcero inoxidableVERIFICADO — etiqueta del catálogo PDF
AccionamientoNeumáticoVERIFICADO — etiqueta del catálogo PDF
ConexiónCon bridasVERIFICADO — etiqueta del catálogo PDF
Serie de origen del catálogoVálvula de mariposaVERIFICADO — sección del catálogo PDF
Página de origen del catálogoPágina 95 del PDFVERIFICADO — asignación de PDF recuperada

Importante: The catalog name includes “High Temperature,” but this record gives no numerical process-temperature limit or pressure-temperature curve. Confirm the offered body, seat, seals and actuator package against the project duty and the approved datasheet and order drawing.

Revisión de ingeniería

What must match before the valve and actuator are specified

For high-temperature service, check the process limits at the valve separately from the temperature around the actuator. The five checks below turn the catalog identity into a configuration that can be evaluated against the real duty.

Process duty and operating envelope

Define the duty—on/off isolation, throttling, bypass or another function—together with medium composition and phase, solids, corrosion or erosion risk, cycle frequency and required shutoff. Provide minimum, normal and maximum process temperature, design and operating pressure, maximum differential pressure, and any start-up, upset or vacuum case. Ask for the allowable pressure at the maximum temperature for the exact offered valve; the catalog name does not define this envelope.

Seat, trim and leakage

Confirm the exact body and disc/shaft grades, seat construction and material, packing, and body seals. “Stainless steel” in the catalog title is not a grade or a complete wetted-parts schedule. Soft and metal seats have different temperature limits, leakage behavior and operating torque; do not assume either from the product name or image. Require the seat and body pressure-temperature limits plus the specified leakage class and direction for the service.

Flanged fit-up and disc clearance

Confirm nominal size, flange standard and pressure designation, facing, bolt pattern, face-to-face dimension, and the gasket arrangement specified for the valve design. Check the mating pipe and flange bore against the disc sweep through full travel, including any liner, reducer or adjacent equipment. Where required by the valve design or service, state the installation orientation and flow direction; provide the expected piping loads at the valve and the available space for actuator access, removal and routine valve maintenance. Have allowable external loads and service clearances confirmed on the approved dimension drawing before ordering.

Actuator temperature and heat path

Do not equate process temperature at the valve with the allowable ambient temperature at the actuator. Record the maximum temperature around the actuator and its solenoid, positioner, limit switches and tubing. Heat may reach the mounting area through the valve body, neck and stem, as well as by radiation or hot surroundings. Ask the supplier whether an approved stem extension, thermal spacer, heat shield or remote mounting is required, and have the arrangement and limits shown on the assembly drawing. The catalog image does not establish thermal isolation.

Pneumatic sizing and air-failure response

Choose double-acting or spring-return actuation to meet the required response on loss of instrument air. State fail-open, fail-closed or fail-in-place behavior separately for air loss, electrical-power loss and control-signal loss; these are not automatically the same event. Confirm minimum and maximum available air pressure. At minimum supply pressure, the actuator must provide the required torque at maximum differential pressure and service temperature; at maximum supply pressure, its output must remain within the valve and shaft allowable torque. Also confirm travel time and cycle rate. Specify the solenoid-valve coil voltage and the electrical command/interface required by the control system. State whether open/closed limit switches and/or position feedback are required, including the required feedback type and interface, and confirm which accessories are included in the offered package. For modulating or throttling duty, state whether a positioner or another supplier-reviewed proportional-control arrangement is required; if so, identify the required control input and interface for supplier review. Do not assume a positioner is needed for on/off service or included in the standard package. A double-acting actuator alone has no inherent spring-driven fail position; any stored-air or lock-up arrangement must be specified and verified for the required response.

Preguntas del comprador

High-temperature butterfly valve: buyer questions

These points resolve the main gaps between a catalog name and an order-ready valve assembly.

What does “High Temperature” confirm?

No numerical limit. It is part of the supplier catalog name. The recovered catalog record on PDF page 95 does not state a process-temperature limit, pressure-temperature curve or exact seat material. Obtain the model-specific datasheet and confirm pressure and temperature together for the offered body, trim and seat.

Are the valve and actuator temperature limits the same?

No. Process temperature applies to the valve’s wetted and pressure-containing components; the actuator and its accessories have their own operating and ambient limits. Check the temperature at the actuator location and heat transfer from the valve. Any extension, spacer or heat shield must be approved for the exact assembly.

Does pneumatic actuation define the fail position?

No. The catalog identifies pneumatic actuation but does not state whether the actuator is double-acting or spring-return, or what position it takes on air loss. Specify the required response to loss of instrument air, electrical power and control signal, then confirm the actuator and control circuit that provide it.

What must be checked at the mating flanges?

Provide the nominal size, flange standard and pressure designation, facing, bolt pattern, face-to-face dimension and valve-specified gasket arrangement. The pipe and flange bore must leave room for the disc throughout full travel. Confirm the fit against the approved dimension drawing.

Consulta técnica

Solicitar revisión de configuración

Use this inquiry to identify the exact offered assembly. Request a model-specific datasheet and dimension drawing showing the valve pressure-temperature envelope, seat and sealing materials, actuator temperature limits, mounting arrangement, fail response and flange interface. See VALMORA Valve Resources & Technical Document Support for the process to request datasheets, drawings and IOM files. The catalog label alone is not a technical approval for the duty.

Fields marked * are required.