Electric actuation · process-control selection
Válvula de control eléctrica
The supplier catalog illustrates several products labeled Válvula de control eléctrica. These are reference configurations, not one model with a published common pressure rating or flow coefficient. For a modulating duty, start with minimum, normal and maximum flow at the corresponding inlet and outlet pressures. Then match the valve, trim and electrical actuator to the control loop and site conditions.
Send your process conditions and required control behavior for a configuration-specific quotation.
- Catalog identity: electric control valve
- Selection basis: flow, pressure drop and control duty
What the published catalog establishes
Electric Control Valve: reference scope and open data
In the illustrated Serie de válvulas de control, the supplier labels more than one assembly “Electric Control Valve.” The pictures establish the product category and show different arrangements; they do not identify a single order-ready model. The pages reviewed do not assign a matching Cv/Kv curve, trim drawing, pressure-temperature rating or electric actuator datasheet to each pictured example.
Use the catalog to identify the intended product, then request the exact valve-and-actuator datasheet for the service below.
| Artículo | Lo que está documentado | What the quotation must resolve |
|---|---|---|
| Identidad del producto | Electric Control Valve in the Control Valve Series (supplier catalog, physical PDF pp. 100–101; printed pp. 190–191) | Confirm the exact offered valve model, matching electric actuator model, datasheet revision, and the catalog figure or assembly drawing used for this quotation. |
| Actuation shown | Electric drive on the catalog-labeled examples | Electrical supply, interface and actuator model not specified by the picture |
| Valve design and trim | Several pictured arrangements; no shared valve construction specified | Request the proposed body/trim drawing, characteristic and leakage data |
| Capacity and operating limits | No matched Cv/Kv, pressure-temperature table or travel curve on these illustrated pages | Size using duty cases and offered valve/trim data |
| Connection, materials and documentation | Not established as order specifications by the label | Confirm exact DN/NPS, PN/Class if required, ends, grades and inspection records |
Para realizar el pedido: the chosen model, materials, valve dimensions, actuator, duty rating and tests belong on a project-specific datasheet and approved drawing—not on an inference from a catalog photograph.
From operating case to technical quotation
Size the valve for the process—not just the line size
Start by deciding whether the valve must regulate a variable flow or mainly open and close. Continuous throttling needs a valve characteristic and usable travel across the operating range; an on/off service may call for a different assembly. For a modulating valve, the inlet and outlet pressure at each flow case determine the available pressure drop. The largest DN or highest fully open Cv is not automatically the best regulating choice.
Use the five inputs below to request a sized valve-and-actuator proposal. Values such as Cv/Kv, rangeability, allowable differential pressure and leakage are selection results or offered specifications—not claims established for these catalog images.
Flow and pressure cases
State the controlled variable (flow, pressure, temperature or level), whether regulation is continuous, and minimum / normal / maximum flow with units. For each case give upstream pressure P1, downstream pressure P2 and operating temperature, preferably in a compact three-row duty table. Indicate whether pressures are gauge or absolute. Include fluid phase and relevant properties (for liquids, density, vapor pressure and viscosity; for gases or steam, composition and thermodynamic conditions).
Pressure and mechanical envelope
Provide operating and design pressure/temperature separately, including transient, vacuum and shutoff differential-pressure cases where relevant. Specify line size DN/NPS and project-specified PN/Class, but do not treat a pressure class as the allowable pressure at every temperature. Confirm the offered valve’s material-dependent pressure-temperature rating and end connection against the piping specification.
Body, trim, sealing and ends
Identify the process fluid and composition, corrosion/erosion or solids concern, body and wetted trim material requirements, end connection and applicable dimensional standard. If tight shutoff matters, request a defined seat leakage class/test rather than assume a throttling valve is bubble-tight. Flange dimensions, face-to-face, flow direction, weight and installation space should be checked against the proposed drawing. Confirm the permitted mounting orientation, valve-and-actuator weight and support loads, local handwheel access, and maintenance/removal clearances against the proposed assembly drawing.
Electrical actuator and control loop
State AC/DC supply voltage and frequency, control command (for example analog input or fieldbus, if specified by the plant), required position feedback, local override, stroke time and expected modulation frequency. The proposed actuator must match valve stroke/travel and thrust or torque under the maximum operating differential pressure. Specify enclosure, ambient conditions, hazardous-area classification if applicable, and the required response to signal loss and separately mains-power loss.
Inspección y documentos
Request the valve/actuator assembly drawing, selected trim and Cv/Kv characteristic, wiring/I/O details, material and test-document scope, inspection/witness requirements and quantity. Where required, state the pressure and seat-leakage tests, applicable acceptance criteria, material certificate scope, marking and third-party witness points in the RFQ. Include project standard editions where mandated, target delivery date and delivery destination/terms. Certificates, test records, availability and lead time must be quoted for the specific offered assembly; they are not implied by the catalog label.
Selection decisions that change the specification
Three checks before approving a valve-and-actuator package
These checks help avoid a motorized valve that physically fits the line but cannot regulate the process or behave safely under plant failures.
Can the valve control at low flow?
If the valve is sized only for peak flow, normal operation may take place near the seat, with little controllable travel. Ask for the calculated required Cv/Kv at minimum, normal and maximum flow and the proposed opening/travel at each case. A nominal pipe diameter alone cannot answer this. Compare the proposed inherent characteristic with the process pressure-drop behavior.
Is the pressure drop severe?
For hot liquids or high differential pressure, check vapor pressure, potential cavitation or flashing and noise before specifying trim. Flashing may persist where downstream pressure is below the liquid vapor pressure; simply choosing a larger motor will not solve it. Ask the supplier to evaluate the actual duty using the chosen valve’s recovery and trim data, not a generic claimed anti-cavitation rating.
What happens when power disappears?
Loss of control signal and loss of mains supply are different failure cases. An electric actuator does not inherently drive the valve to a safe position without power; that may require a proven reserve-power or other engineered arrangement. Define the required fail position, time and restart behavior, then require the offered actuator/control package to document how it meets each condition.
Reference photos · actual supplier catalog
Electric control-valve examples in the source catalog
The supplier illustrates different electric control-valve assemblies. These are different pictured examples, not interchangeable configurations of a verified single model. Images show appearance only; consult the offered drawing for valve internals, dimensions, installed height and clearances.
Related control-valve options
Check drive type and service before choosing an alternative
Use these catalog-labeled alternatives when the plant utility, control method or temperature duty changes. The linked pages describe different catalog identities; their materials, ratings and performance must be checked independently.
Válvula de control neumática de acero forjado
A pneumatic actuation route to review when instrument air and the specified pneumatic control arrangement are available. Compare fail action, utility supply and maintenance—not just actuator appearance.
Válvula de control eléctrica de alta temperatura
A separate catalog entry for high-temperature service. The name does not establish a temperature limit; request the specific pressure-temperature and actuator thermal arrangement.
Válvula de control neumática de diafragma
A diaphragm-operated pneumatic alternative. Compare the required stroke, actuator force, air supply and emergency position against the electric option.
Send a project-specific control-valve inquiry
Request an Electric Control Valve quotation
Tell us the control duty and conditions you already have. For a reliable selection, the most useful starting document is a minimum/normal/maximum operating-case sheet with flow, P1, P2 and temperature. Include the power and signal requirements if known. If values or drawings are still missing, identify them rather than selecting a catalog photograph as a final model.
- Control objective, medium/composition and phase
- Minimum, normal and maximum flow (units), matching P1/P2 and temperature
- Design/operating pressure-temperature, DN/NPS, PN/Class and end connection
- Body/trim/seat and leakage requirements; solids or corrosion concerns
- Supply voltage, command/feedback, stroke speed, control frequency and power-loss behavior
- Quantity, destination, required drawings, inspection/test documents and target delivery