Vollhub-Sicherheitsventil mit Isoliermantel und Gegendruckkompensation

BWA42Y insulated-jacket, back-pressure-balanced full-lift safety relief valve catalog image.

Der wiederhergestellte englische Katalog führt BWA42Y as the Vollhub-Sicherheitsventil mit Isoliermantel und Gegendruckkompensation on PDF page 106. The designation and design descriptors identify the catalog record; set pressure, relieving capacity, back-pressure limits and jacket details must be confirmed for the offered configuration.

Katalogidentität

BWA42Y in the Safety Valve series

The English catalog prints “BWA42Y” beside this product name on PDF page 106. It appears in the Safety/Relief Valve family under the Safety Valve series. Treat BWA42Y as the catalog designation until the offered datasheet and order drawing confirm the exact model and revision.

Katalogbezeichnung

BWA42Y, as printed in the recovered English product catalog. Confirm the offered model code and revision against the current datasheet and approved drawing.

Produktfamilie

Safety/Relief Valve. The parent category remains the route for browsing the wider safety and relief valve range.

Catalog series and image source

Safety Valve series; recovered English product catalog, PDF page 106.

Katalogbelege

Was der Katalog tatsächlich identifiziert

The product label names three design descriptors—insulated jacket, back-pressure balanced and full-lift. These words identify the catalog configuration but do not provide numeric performance limits or prove a specific internal balance mechanism.

FeldIm Katalog dokumentierter WertNachweisstatus
KatalogbezeichnungBWA42YVERIFIED — printed in the PDF product label
Named design descriptorsInsulated jacket; back-pressure balanced; full-liftVERIFIED — catalog product name only
KatalogquelleSafety Valve series; recovered English product catalog, PDF page 106VERIFIED — catalog page and product-image mapping

Wichtig: the supplied page-106 evidence does not state set pressure, rated relieving capacity, orifice, nominal size, pressure class, temperature range, material grades, end connections or approvals. Obtain these from the offered datasheet and approved order drawing.

Nachweisgrenze

Performance and construction still need proof

The catalog record establishes the name and identity, not an order-ready pressure-relief device. Keep the relief-duty basis separate from the jacket and mechanical construction details.

Relief performance

Jacket and offered construction

Technische Prüfung

Build the RFQ around the relief duty

A safety relief valve is sized for a defined overpressure case, not selected from its product name or inlet size alone. The protected equipment, relieving scenario and fluid properties establish the duty; the discharge system and jacket arrangement determine whether this catalog configuration can be offered for it.

Zu schützendes Equipment und Entlastungsfall

Identify the protected vessel, line or equipment; provide its MAWP or governing design limit, credible overpressure scenarios, and the required relieving mass flow or volumetric flow with its value and unit. State the corresponding relieving pressure and temperature, fluid phase at relief—gas/vapor, liquid or two-phase—relevant fluid properties, and the sizing calculation basis.

Set pressure and inlet conditions

Provide normal operating pressure, proposed valve set pressure, relieving pressure and temperature, allowable accumulation during relieving above the protected equipment's MAWP (or applicable design pressure limit), and allowable overpressure at the valve inlet above the valve's set pressure. State the governing code/design basis and the pressure reference used for each limit, plus inlet pressure loss. The catalog does not state a set-pressure range or rated capacity.

Back-pressure profile and discharge header

Separate superimposed constant back pressure, superimposed variable back pressure and built-up back pressure at the required relieving flow. Identify common headers and other devices that may discharge simultaneously. Ask the supplier to state the allowable limit and any effect on set pressure, lift and capacity for the offered construction.

Jacket and thermal duty

Clarify whether “insulated jacket” means passive insulation or a heated cavity. If heated, state the available utility, supply/return pressure and temperature, jacket connection arrangement, coverage, vent/drain needs and separate jacket design/test basis. Confirm whether adjacent inlet/outlet piping also needs heat tracing.

Fluid, materials and project documents

Give fluid composition, concentration, phase, viscosity, solids, crystallization/solidification and corrosion/erosion risks. Confirm body, trim, seat/seal and any balance-element materials, size and end connections, governing code/edition, jurisdiction, approval scope, tests, inspection and witness requirements.

Anwendungsgrenze

Three decisions the catalog name does not settle

The name points to a jacketed, back-pressure-balanced, full-lift configuration. It does not establish the actual service limits. Use these distinctions to prepare the technical review.

Does the jacket add heat or only slow heat loss?

If the process medium becomes viscous, crystallizes or deposits as it cools, a heated jacket may help maintain the flow path. Passive insulation only slows heat loss; it does not supply heat. Confirm the supplied arrangement, heated zones, utility and separate jacket rating. Do not assume the seat, nozzle or adjoining piping is heated because the catalog uses “insulated jacket.”

What kind of back pressure will the outlet see?

Superimposed back pressure exists before the valve opens; built-up back pressure develops as relieving flow passes through the discharge piping. Variable pressure from a common header is different from a steady outlet pressure. A balanced design may reduce the effect of back pressure, but it is not unlimited; the supplier must confirm the mechanism, allowable pressure and performance for the actual duty. If bellows are used, also confirm bellows material/limit and bonnet-vent arrangement.

Does full-lift establish a capacity?

No. “Full-lift” is a catalog design descriptor, not a rated relieving-capacity figure or certified flow coefficient. Capacity depends on the offered orifice and valve construction plus fluid phase/properties, set pressure, overpressure, temperature and back pressure. Use the manufacturer’s sizing and certification documents for the selected tag.

Bestätigung durch den Lieferanten

What the quotation should document

The catalog label is not enough for technical approval. Review the offer against the same relief case and require the following details in the supplier’s return package.

Model and jacket construction

Confirm the BWA42Y designation and revision, the actual back-pressure balancing mechanism, and whether the jacket is passive insulation or a heated cavity. The datasheet and drawing should identify jacket coverage, connection locations and any heating medium. Do not assume bellows unless the offered drawing identifies them.

Relief performance and sizing basis

The return package should state the offered set pressure and orifice; rated relieving capacity value with its mass- or volumetric-flow unit, applicable fluid phase/properties and relieving conditions; and the sizing/certification basis. It should separately identify allowable accumulation during relieving above the protected equipment's MAWP (or applicable design pressure limit) and allowable overpressure at the valve inlet above the valve's set pressure, plus allowable back pressure for the specified relieving case. Do not substitute values from another model or series.

Materials and pressure boundaries

Confirm process-side body, trim, seat/seal and balance-element materials, pressure-temperature limits, end connections and dimensions. If the jacket is a heated cavity, provide its separate design pressure/temperature, test basis, utility and drainage/vent details.

Code, approvals and inspection records

Identify the governing code and edition, jurisdiction, certificate or stamp and approval scope for this exact model/tag. List the required pressure/leakage tests, inspection reports, witness points and marking; availability and applicability must be stated in the quotation.

Technische Anfrage

Request a BWA42Y configuration review

Reference catalog designation BWA42Y and provide the known relief-duty and jacket data. Mark unknown values as pending; do not estimate set pressure, capacity, back-pressure limits or certification. The existing product inquiry form remains the submission route.